75kVA Three Phase Pad Mounted Transformer
The 75kVA pad-mounted transformer is tailored for utility customers in Canada, featuring a primary voltage of 25kV and a secondary voltage of 480/277V. It strictly adheres to local standards, including CSA C227.4 and CSA C802.1, ensuring optimal efficiency values. Notably, both the high and low-voltage windings are crafted from aluminum.
- Primary Voltage Ratings 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2, 24.94, 26.25, 33 or others
- Secondary Voltage Ratings 208GrdY/120;416GrdY/240 or Customized
- H.V. Tap Range ± 2×2.5% HV taps or others
- Type Loop Feed or Radial Feed
- BIL 30/95kV
- Standards CSA C227.4 , CSA C802.1
- Application EV charging, Utility, BESS
- Power Rating 45kVA
- Certificate UL/cUL, CSA, CESI, and other certificates.
- Cooling Method ONAN, ONAN/ONAF, KNAN, KNAN/KNAF
- Oil Minerial Oil or FR3
- Opeartion Step Down & Step Up
Technical Specifications
Optional Configurations
Packing and Shipping
Test
Routine Test
Application
Technical Specifications
75kVA Three Phase Pad Mounted Transformer
Technical Specifications
Accessories
Rated Power | 75 kVA |
Rating Primary Voltage | 11950Delta or Customized |
Secondary Voltage | 480GrdY/277 208GrdY/120 400GrdY/230 Customized(208Y/120 V to 4,160 V) |
Frequency | 50/60Hz |
Vector Group | Dyn1/Yyn0/Dyn11/Dyn5 |
Winding Material | Aluminum/Copper |
Efficiency | As IEEE,Doe 2016,CAS Std or Customized |
Impedance Voltage | Nominal 3.5% or Customized 1.1-5.75% |
Altitude | ≤1,000m or Customized |
Color | ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized etc |
Tank material | Mild Steel, 304 Stainless Steel |
Insulating Oil Weight | 205 kg |
Total Weight | 650 kg |
Outline Dimensions(L×W×H)in. | 900×710×1100 (mm) |
Lifting Lug | ELSP Fuse |
Hinged Door | BAY-O-NET Fuse |
Parking Bracket | Tap Changer |
Tank Cover | Oil Level Gauge |
L.V Bushing (4-Hole ) | Pressure Relief Valve |
Two/Four Position Load break Switch | Vacuum Pressure Gauge |
HV Grounding Copper Bar | Terminal Block |
Temperature Indicator | Door Handle |
H.V Bushing Well(15kV) | Ground Strap |
Grounding Copper Bar | Nameplate |
1"'Drain Valve With 3/8" Sampler | IR Window |
1" Upper Fill Valve Filter Press Connection | Terminal Box |
Non-PCB decal | High Voltage Warning Signs |
Optional Configurations
75kVA Three Phase Pad Mounted Transformer
NPC ELECTRIC transformers offer pad mounted transformer a wide range of optional features to meet the diverse needs of electrical systems. The optional specifications for a 75kVA Three Phase Pad Mounted Transformer may include various customizable features to meet specific operational needs. These options typically involve different voltage ratings (both high and low voltage), various enclosure protection levels (such as IP55 or NEMA 3R), and cooling methods (like ONAN for optimal temperature rise management).
Additional options may include customizable load connection types (Delta-Delta, Wye-Wye, Delta-Wye), advanced protection devices (overload and short-circuit protection), and smart monitoring systems for real-time performance tracking. Furthermore, customers may select enhanced durability options, corrosion-resistant coatings for harsh environments, and reduced noise designs. These specifications allow the transformer to be tailored to specific applications and environmental conditions, ensuring reliable and efficient operation.
Packing and Shipping
75kVA Three Phase Pad Mounted Transformer
NPC ELECTRIC three-phase transformers are designed to be securely packaged for sea freight transport, ensuring safe delivery across long distances. For this purpose, The 75kVA Three Phase Pad Mounted Transformer is typically packed and shipped to ensure its protection during transportation and to comply with international shipping standards. The transformer is securely placed on a sturdy wooden pallet or skid to prevent any movement during transit. It is then wrapped with weather-resistant plastic or shrink wrap to protect it from moisture, dust, and other environmental factors. For additional safety, the transformer may be enclosed in a wooden crate or reinforced container, especially for long-distance or international shipments.
Shipping is usually done via flatbed trucks or containers, depending on the destination and transport logistics. The packaging is designed to protect the transformer from mechanical damage, such as impacts or vibrations, while maintaining its integrity. All relevant shipping labels, including the weight, dimensions, and handling instructions, are clearly marked on the packaging to ensure smooth handling upon arrival. If shipping internationally, customs documentation and export packaging requirements will also be addressed to facilitate hassle-free clearance.
Shipping is usually done via flatbed trucks or containers, depending on the destination and transport logistics. The packaging is designed to protect the transformer from mechanical damage, such as impacts or vibrations, while maintaining its integrity. All relevant shipping labels, including the weight, dimensions, and handling instructions, are clearly marked on the packaging to ensure smooth handling upon arrival. If shipping internationally, customs documentation and export packaging requirements will also be addressed to facilitate hassle-free clearance.


32
32 years of industry experience
Test
75kVA Three Phase Pad Mounted Transformer

Progress test
NPC Electirc manufacture pad mounted transformer have the strict quality control from the raw material stage, Each 75 kVA transformer undergoes a series of routine tests before it leaves the factory, in strict adherence to the ANSI/IEEE C57.12.90 standard. These tests are critical to ensuring the transformer's performance and safety. The routine tests consist of the following:
Ratio tests on each connection.
(b) Polarity verification.
(c) Assessment of no-load losses at 105% rated voltage, corrected to 85°C.
(d) Evaluation of exciting current at 105% rated voltage.
(e) Measurement of load losses and impedance at rated current, conducted on the rated voltage connection, and corrected to 85°C. It's important to note that this test is performed on the high-voltage connection that exhibits the highest measured loss value.
(f) Applied voltage tests.
(g) Induced voltage assessments.
(h) Transformer tank leak-detection test, conducted on each transformer tank to validate the integrity of the welds. This test is also performed on the final assembled unit without the pressure relief device.
Ratio tests on each connection.
(b) Polarity verification.
(c) Assessment of no-load losses at 105% rated voltage, corrected to 85°C.
(d) Evaluation of exciting current at 105% rated voltage.
(e) Measurement of load losses and impedance at rated current, conducted on the rated voltage connection, and corrected to 85°C. It's important to note that this test is performed on the high-voltage connection that exhibits the highest measured loss value.
(f) Applied voltage tests.
(g) Induced voltage assessments.
(h) Transformer tank leak-detection test, conducted on each transformer tank to validate the integrity of the welds. This test is also performed on the final assembled unit without the pressure relief device.

Design Tests
All transformer will be test after finished the production, test items as below:
♦ Insulation Power Factor:
♦ Ratio, Polarity, and Phase Relation:
♦ Winding Resistance:
♦ Impulse Tests:
♦ On load Loss Test:
♦ No Load Loss Test
♦ Leak Test:
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)
♦ Insulation Power Factor:
♦ Ratio, Polarity, and Phase Relation:
♦ Winding Resistance:
♦ Impulse Tests:
♦ On load Loss Test:
♦ No Load Loss Test
♦ Leak Test:
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)

Transformer Factory Acceptance Test
NPC Electric will tests made for quality control by the manufacturer on every device or representative samples, or on parts or materials as required, to verify during production that the product meets the design specifications.
Routine Test
Insulation Power Factor
Ratio, Polarity, and Phase Relation
Winding Resistance
Impulse Tests
On load Loss Test
No Load Loss Test
Test Standard As Below:
IEEE C57.12.00 & IEEE C57.12.90 (Liquid-Immersed)
IEEE C57.12.01 & IEEE C57.12.91 (Dry-Type)
IEEE C57.12.01 & IEEE C57.12.91 (Dry-Type)
*These comprehensive tests ensure that each transformer meets performance standards and operates reliably under various conditions.

Application
EV charging, Utility, BESS
Factory View
● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions
Product Packaging
Related Products
FAQ From Customers
-
What is a Transformer?A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
-
What are the main uses of a transformer?The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
-
Do you have UL listed?Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.
Welcome your inquiry
Honesty, Integrity, Frugality, Activeness and Passion